-A +A

<none>

AS02 - Arc Light and Pressure Point Sensor

You are here

Production

Generation

Distribution

Distribution

industrie

Industry

ferroviere

Railway

AS02 - Arc Light and Pressure Point Sensor

Arc Flash Sensors

The AP900 series, arc flash protection relays provides a choice of different types of arc sensors to be utilised in different units and different switchgear types according to specific application requirements.

Available sensor types are arc light point sensors, arc light and pressure point sensors and arc light fibre optic loop sensors.

Arc light and pressure point sensors are typically installed in metal clad compartments providing quick accurate location of the faulted area.

Technical data:

  • Light and pressure Intensity thresholds: 8,000 lux
  • Detection radius: 180 degrees
  • Pressure threshold setting (fixed1): 0.2 bar above ambient pressure
  • Mechanical protection for photodiode element: IP 60
  • Mechanical protection for pressure element: IP40
  • Maximum sensor cable length per sensor channel: 200 meters
  • Operating temperature: -20...+85  ̊C

1 A standard atmospheric pressure is 1 bar.

Sensor type dependencies:

Product family: 
Arc Flash Detectors & Sensors

AP900 Series


Training

Find out about our training

Prescribers Maintenance and commissioning equipment Systems Application and customised training.

Downloads

Discover our documentary base.

Our Values

ICE SAS is built around strong values shared by all giving meaning to our actions for more than 75 years.