PDZI9000
ferro

PDZI9000

Catenary protection - 25 kV or 2x25 kV

Protects 25 kV or 2×25 kV AC catenary systems at 50 or 60 Hz.

Embedding various protection functions, including a distance function [21] combined with a large event recording capacity, our PDZI9000 facilitates the operation of your AC railway electrical network.

Thanks to its hybrid acquisition via CTs or IEC 61850-9-2 «Sampled Values», it is now possible to protect catenaries operated in parallel connected to the same transformer by means of a patented summed current management.

, , , ,
High resolution colour touch screen
Embedded web server
Instantaneous tripping time < 30 ms
Sampling rate: 6.4 kHz
Operating temperature: -5 °C to 55 °C
Communication interfaces
Communication protocols
Mesures and operations
Mounting
Power supply
Type of option cards
Current inputs
  • 3
Voltage outputs
  • 2
Disturbance records
  • 32
Event logs
  • 1000
Digital inputs
  • 18
Digital outputs
  • 28
Dedicated trip outputs
  • 2
Watchdog output
  • 1
Indication LEDs
  • 16
Number of optional modules
  • 1
  • 21 — Underimpedance
  • 21FL — Underimpedance fault locator
  • 21SUM — Low-impedance summation
  • 27 — Undervoltage
  • 50 — Instantaneous overcurrent
  • 50BF — Breaker failure
  • 51 — Time overcurrent
  • 51DPR — Power swing detection
  • 59 — Overvoltage
  • 59H — Harmonic overvoltage
  • 67 — Phase directional overcurrent
  • 74TC — Trip circuit supervision
  • 79 — Autorecloser
  • 86 — Locking-out function
  • 87 — Differential function
  • FL — Fault locator